Room temperature controller generates the setpoint for the supply air temperature controller.
Up to 4 room sensors can be connected. Room temperature is an averaged value, which is calculated according configured sensors.
Settings and configuration for Room cascade control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|...| Room cascade | … | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Room temperature sensor |
| No | 1 | 2 | 3 | 4 | |
- |
|
Calculation mode room temperature |
| Average | Min value | Max value | Weighted average | |
* Option available if the number of room temperature sensors is more than 1. Weighted average - average of the min and the max values |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Room temperature 1 |
Any available I/O |
||
Supply air temperature |
|||
PI Settings |
|||
Configuration > PID controllers > Room |
|||
P-band |
[100] oC |
PI settings for the room controller |
|
I-time |
[300] s |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
||
Data & Settings > Temperature control > Room controller |
|||
Room temperature |
__ oC |
Actual room temperature |
|
Setpoint room |
[21.0] oC |
Setpoint |
|
Actual setpoint room |
__ oC |