Access 5.x  | 
Control modes > Room cascade  | 
Room temperature controller generates the setpoint for the supply air temperature controller.
Up to 4 room sensors can be connected. Room temperature is an averaged value, which is calculated according configured sensors.
Settings and configuration for Room cascade control  | 
|||
Variable  | 
Available options & Selection  | 
Note  | 
|
Activate temperature control type  | 
|||
Configuration > Functions > Function activation  | 
|||
Temperature control type  | 
|...| Room cascade | … |  | 
-  | 
|
Activate sensors & additional options  | 
|||
Configuration > Functions > Temperature control  | 
|||
Room temperature sensor  | 
| No | 1 | 2 | 3 | 4 |  | 
-  | 
|
Calculation mode room temperature  | 
| Average | Min value | Max value | Weighted average |  | 
* Option available if the number of room temperature sensors is more than 1. Weighted average - average of the min and the max values  | 
|
Supply air temperature sensor  | 
|Yes | No |  | 
-  | 
|
Configure inputs  | 
|||
Configuration > I/O allocation settings > Analog inputs >  | 
|||
Room temperature 1  | 
Any available I/O  | 
||
Supply air temperature  | 
|||
PI Settings  | 
|||
Configuration > PID controllers > Room  | 
|||
P-band  | 
[100] oC  | 
PI settings for the room controller  | 
|
I-time  | 
[300] s  | 
||
Operational settings  | 
|||
Data & Settings > Temperature control > Supply air controller  | 
|||
Supply air temperature  | 
__ oC  | 
Actual supply air temperature  | 
|
Min limit supply air  | 
[12.0] oC  | 
Limits of the supply air temperature.  | 
|
Max limit supply air  | 
[30.0] oC  | 
||
Actual setpoint supply air  | 
__ oC  | 
||
Data & Settings > Temperature control > Room controller  | 
|||
Room temperature  | 
__ oC  | 
Actual room temperature  | 
|
Setpoint room  | 
[21.0] oC  | 
Setpoint  | 
|
Actual setpoint room  | 
__ oC  | 
||