Access 5.x |
Control modes > Room (summer) else supply air |
This temperature control mode combines Room cascade and Supply air outdoor compensated modes.
Summer/winter mode function is utilized for switching.
In summer - room cascade mode is active and room temperature controller generates the setpoint for the supply air temperature controller.
In winter - supply air outdoor compensated mode is active. Setpoint for supply air temperature is determined by outdoor temperature and dependency curve.
Settings and configuration for Room (summer) else supply air control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|...| Room (summer) else supply air | … | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Room temperature sensor |
| No | 1 | 2 | 3 | 4 | |
- |
|
Calculation mode room temperature |
| Average | Min value | Max value | Weighted average | |
* Option available if the number of room temperature sensors is more than 1. Weighted average - average of the min and the max values |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Summer/Winter mode |
|Yes | No | |
Function switches to | Yes | automatically in this control mode |
|
Type of switch summer/winter |
| Calendar | Changeover | Digital input | Outdoor temperature | |
[Outdoor temperature] is the default option |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Room temperature 1 |
Any available I/O |
||
Supply air temperature |
|||
PI Settings |
|||
Configuration > PID controllers > Room |
|||
P-band |
[100] oC |
PI settings for the room controller |
|
I-time |
[300] s |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Setpoint outdoor curve |
> |
Setpoint curve for winter |
|
Neutral zone (C°) |
[0.0] oC |
Width of neutral zone |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
||
Data & Settings > Temperature control > Room controller |
|||
Room temperature |
__ oC |
Actual room temperature |
|
Setpoint room |
[21.0] oC |
Setpoint for summer |
|
Outdoor temp for switch between summer/winter |
[13.0] oC |
Summer / winter mode switch settings |
|
Outdoor temp hysteresis for switch between summer/winter |
[1.0] oC |
||
Actual setpoint room |
__ oC |
||
Curve point |
Outdoor temperature (C°) |
Setpoint supply temperature (C°) |
|
Setpoint outdoor curve |
|||
Data & Settings > Temperature control > Supply air controller > Setpoint outdoor curve |
|||
Point 1 |
[-20] oC |
[22] oC |
|
Point 2 |
[5] oC |
[20] oC |
|
Point 3 |
[20] oC |
[20] oC |
|
Point 4 |
[30] oC |
[22] oC |
|
Setpoint outdoor curve |
|||
Related topics:
Chapter info
Last reviewed: 9/16/2021
Access version: 4.5-1-01 (2913)