Access 5.x |
Control modes > Supply air |
The supply air temperature is kept at the fixed setpoint (setpoint compensation can apply).
Settings and configuration for Supply air control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
| Supply air | … | |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Supply air temperature sensor |
|Yes | No | |
- |
|
Configure input |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Supply air temperature |
Any available I/O |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Setpoint supply air |
[18.0] oC |
Setpoint |
|
Neutral zone (C°) |
[0.0] oC |
Width of neutral zone |
|
Setpoint adjustment |
[0] oC |
||
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
Related topics: