Access 5.x  | 
Control modes > Supply air outdoor compensated  | 
The supply air temperature setpoint is outdoor temperature compensated using a control curve with 4 node points.
Settings and configuration for Supply air outdoor compensated control  | 
|||
Variable  | 
Available options & Selection  | 
Note  | 
|
Activate temperature control type  | 
|||
Configuration > Functions > Function activation  | 
|||
Temperature control type  | 
|...| Supply air outdoor compensated |...|  | 
-  | 
|
Activate sensors & additional options  | 
|||
Configuration > Functions > Temperature control  | 
|||
Outdoor temperature sensor  | 
| No | Intake | Outdoor | Outdoor + Intake air |  | 
-  | 
|
Supply air temperature sensor  | 
|Yes | No |  | 
-  | 
|
Configure inputs  | 
|||
Configuration > I/O allocation settings > Analog inputs >  | 
|||
Outdoor temperature  | 
Any available I/O  | 
||
Supply air temperature  | 
|||
Operational settings  | 
|||
Data & Settings > Temperature control > Supply air controller  | 
|||
Supply air temperature  | 
__ oC  | 
Actual supply air temperature  | 
|
Setpoint outdoor curve  | 
>  | 
-  | 
|
Neutral zone (C°)  | 
[0.0] oC  | 
Width of neutral zone  | 
|
Setpoint adjustment  | 
[0] oC  | 
||
Min limit supply air  | 
[12.0] oC  | 
Limits of the supply air temperature.  | 
|
Max limit supply air  | 
[30.0] oC  | 
||
Actual setpoint supply air  | 
__ oC  | 
||
Curve point  | 
Outdoor temperature (C°)  | 
Setpoint supply temperature (C°)  | 
|
Setpoint outdoor curve  | 
|||
Data & Settings > Temperature control > Supply air controller > Setpoint outdoor curve  | 
|||
Point 1  | 
[-20] oC  | 
[22] oC  | 
|
Point 2  | 
[5] oC  | 
[20] oC  | 
|
Point 3  | 
[20] oC  | 
[20] oC  | 
|
Point 4  | 
[30] oC  | 
[22] oC  | 
|
Setpoint outdoor curve  | 
|||
  | 
|||