Control modes > Extract (summer) else supply air |
This temperature control mode combines Extract air cascade and Supply air outdoor compensated modes.
Summer/winter mode function is utilized for switching.
In summer - extract air cascade mode is active and extract temperature controller generates the setpoint for the supply air temperature controller.
In winter - supply air outdoor compensated mode is active. Setpoint for supply air temperature is determined by outdoor temperature and dependency curve.
Settings and configuration for Extract air (summer) else supply air control |
|||
Variable |
Available options & Selection |
Note |
|
Activate temperature control type |
|||
Configuration > Functions > Function activation |
|||
Temperature control type |
|…| Extract air (summer) else supply air |…| |
- |
|
Activate sensors & additional options |
|||
Configuration > Functions > Temperature control |
|||
Extract air temperature sensor |
|Yes | No | |
- |
|
Supply air temperature sensor |
|Yes | No | |
- |
|
Summer/Winter mode |
|Yes | No | |
Function switches to | Yes | automatically in this control mode |
|
Type of switch summer/winter |
| Calendar | Changeover | Digital input | Outdoor temperature | |
[Outdoor temperature] is the default option |
|
Configure inputs |
|||
Configuration > I/O allocation settings > Analog inputs > |
|||
Extract air temperature |
Any available I/O |
||
Supply air temperature |
|||
PI Settings |
|||
Configuration > PID controllers > Extract |
|||
P-band |
[100] oC |
PI settings for the extract air controller |
|
I-time |
[300] s |
||
Operational settings |
|||
Data & Settings > Temperature control > Supply air controller |
|||
Supply air temperature |
__ oC |
Actual supply air temperature |
|
Setpoint outdoor curve |
> |
Setpoint curve for winter |
|
Neutral zone (C°) |
[0.0] oC |
Width of neutral zone |
|
Min limit supply air |
[12.0] oC |
Limits of the supply air temperature. |
|
Max limit supply air |
[30.0] oC |
||
Actual setpoint supply air |
__ oC |
||
Data & Settings > Temperature control > Extract air controller |
|||
Extract air temperature |
__ oC |
Showing actual extract air temperature |
|
Setpoint adjustment |
[0] oC |
||
Setpoint extract air |
[20.0] oC |
Setpoint for summer |
|
Outdoor temp for switch between summer/winter |
[13.0] oC |
Summer / winter mode switch settings |
|
Outdoor temp hysteresis for switch between summer/winter |
[1.0] oC |
||
Actual setpoint extract air |
__ oC |
||
Curve point |
Outdoor temperature (C°) |
Setpoint supply temperature (C°) |
|
Setpoint outdoor curve |
|||
Data & Settings > Temperature control > Supply air controller > Setpoint outdoor curve |
|||
Point 1 |
[-20] oC |
[22] oC |
|
Point 2 |
[5] oC |
[20] oC |
|
Point 3 |
[20] oC |
[20] oC |
|
Point 4 |
[30] oC |
[22] oC |
|
Setpoint outdoor curve |
|||